
UNIPROOF EIMSwitchboard Electrical Insulation Mat
Switchboard electrical insulation mat
UNIPROOF EIM is a natural rubber insulating mat laid in front of switchboards, switchgear and other live low and medium voltage equipment, to insulate workers standing on it and reduce the risk of electric shock.
- Technical data sheetReadPDF · 1.3 MB
- Test report, MSDSOn request
About UNIPROOF EIM
UNIPROOF EIM insulating matting is a flexible elastomer sheet produced with high-quality natural rubber. It covers floor surfaces in front of switchboards, switchgear, distribution panels and other live medium and low voltage electrical equipment, insulating workers standing on it and reducing the risk of electric shock during live working or maintenance.
It has a corrugated (ribbed) or diamond top surface for anti-slip protection and a rough honeycomb base that stops the mat moving on the floor. Bevelled or flat edges prevent curling and reduce tripping hazards. UNIPROOF EIM is a supplementary protective measure and must be used by skilled workers following safe working procedures.
Advantages
- Enhanced safety design: anti-slip ribbed or diamond top surface and high-friction bottom texture
- Trip prevention: bevelled or flat edges prevent edge curling
- Built to meet dielectric, mechanical, climatic and environmental stresses, including puncture, slip, ageing, flame retardancy, low temperature, acid and oil resistance
- Customisable installation: supplied in standard rolls and can be cut on site
Where it is used
- Low and medium voltage switchboards and switchgear panels
- Substations and transformer rooms
- Motor control centres (MCC) and control panels
- Live working environments up to 36 kV (Class 4)
Specifications
From the UNIPROOF EIM technical data sheet. Check the latest TDS for your submittal.
| Standard | IEC 61111:2009 / BS EN 61111:2009; TNB KEJ08434:2013 (mechanical and climatic properties) |
|---|---|
| Classes | Class 0 to Class 4 (1,000 V to 36,000 V max. working voltage) |
| AC withstand voltage | Class 0: 10 kV AC, 3 min; Class 1: 20 kV AC, 3 min (no breakdown) |
| Hazardous substances | RoHS 2011/65/EU (RoHS 1 and RoHS 2) complied |
| Material | Natural rubber (NR) / SBR elastomer |
| Hardness | 60 ± 5 Shore A |
| Specific gravity | Approx. 1.6 g/cm³ |
| Colour | Black / grey |
| Top surface | Corrugated (ribbed) or diamond plate anti-slip pattern |
| Thickness | 3 / 5 / 6 / 8 / 12 mm |
| Roll size | 1 m x 10 m or 1 m x 6 m (600 mm x 3 m on request for TNB projects) |
Questions about UNIPROOF EIM
Which class of UNIPROOF EIM do I need?
Choose by the maximum working voltage of the equipment, not the withstand voltage. Class 0 covers up to 1,000 V (3 mm), Class 1 up to 7,500 V (5 mm), Class 2 up to 17,000 V (6 mm), Class 3 up to 26,500 V (8 mm) and Class 4 up to 36,000 V (12 mm).
What standard does it meet?
UNIPROOF EIM is tested to IEC 61111:2009 and BS EN 61111:2009, with mechanical and climatic properties to TNB KEJ08434:2013, and complies with RoHS 2011/65/EU. Test reports refer to the samples tested under the stated conditions.
How should the mat be laid and checked?
Lay it flat on a clean, dry floor with no curled edges, covering the full standing area in front of the equipment. Inspect it before each use and do not use a mat that is cut, punctured, blistered, cracked or contaminated with conductive material.
Is the mat enough on its own?
No. UNIPROOF EIM is a supplementary protective measure. Follow the site's safe working procedure and use appropriate PPE.
How do I clean it?
Clean with mild soap and water, avoiding abrasive tools that could cut or scratch the surface pattern. Make sure the mat is completely dry and free of cracks, pinholes or creases before returning it to service.



