A waterstop seals the joint between two concrete pours so water cannot travel along it. Picking one comes down to three questions: does the joint move, where does the waterstop sit in the section, and how much water pressure and movement the structure has to take. The project engineer makes the final call; this guide explains the options so the specification makes sense.
1. Does the joint move?
| Joint type | What happens at the joint | Waterstop to use |
|---|---|---|
| Construction joint (kicker, day-joint in a wall or slab) | Two pours meet; the joint is not meant to open | Construction profile without a centre bulb (UNISTOP® ICJ / ECJ, rubber dumbbell) or a hydrophilic swelling strip (UNISWELL®) |
| Expansion / movement joint | The joint is designed to open and close | Expansion profile with a centre bulb (UNISTOP® IEJ / EEJ, rubber centre bulb) or copper with a fold, plus filler board and sealant |
Swelling strips such as UNISWELL® SW47, SW10 and SW20 are for non-movement construction joints only, fully contained in the concrete. They are not a substitute for a centre-bulb waterstop at an expansion joint.
2. Internal or external?
- Internal profiles (UNISTOP® ICJ, IEJ) are cast in the middle of the wall or slab, half in each pour, with the edge eyelets wire-tied to the reinforcement.
- External profiles (UNISTOP® ECJ, EEJ) sit on the blinding under a base slab, ribs up, centred on the joint and nailed through the outer web to the stop-end formwork. They are easier to place under slabs because they do not need to be held in the middle of the reinforcement.
UNISTOP® PVC waterstop comes in widths of 150, 200, 250 and 320 mm (refer to the TDS for the full profile list), in rolls, with factory-made intersections so less heat jointing is done on site.
3. PVC, rubber or copper?
| Material | Where it suits |
|---|---|
| UNISTOP® PVC | The general choice for basements, tanks, treatment plants and retaining walls. Heat-welded on site; prefabricated intersections available. |
| UNISTOP® NR natural rubber | Joints with larger or cyclic movement, settlement or seismic movement. High elasticity and elongation. |
| UNISTOP® TPR thermoplastic rubber | Lighter than natural rubber and can be welded on site, with prefabricated intersections. |
| UNISTOP® Copper | High water pressure and long design life, e.g. dams and spillways. Phosphorus non-arsenical copper, 1 mm thick. |
| UNISWELL® hydrophilic strip | Construction joints, pipe penetrations, form ties and repairs to existing joints where a cast-in profile cannot be placed. |
4. Details that go wrong on site
- Centre the waterstop on the joint, half in each pour. An off-centre waterstop leaves a short water path on one side.
- Tie it to the reinforcement (internal profiles) so it does not fold over when concrete is placed.
- Compact the concrete fully around it: honeycombing around the flange is the most common leak path.
- Swelling strips need cover: our details show a minimum 50 mm of concrete cover, and the strip bonded with UNISTICK CA on a sound, level surface.
- Expansion joints are a system: waterstop + UNIFLEX® filler board + UNISEAL® sealant. See sealing a concrete joint.
Not sure which profile your drawing calls for? Send the joint detail to us on WhatsApp and we will match the UNISTOP® or UNISWELL® product and send the TDS.
Typical guidance only – not an engineering design. Joint layout, sizes and reinforcement are designed and approved by the project engineer. Refer to each product's TDS.